UL 5107 18 AWG 16 Strand 200 / 450 600V – Nickel Plated

Min/Mult: 250/50

Clear
SKU: W51071816-N Categories: ,

Description

APPLIANCE WIRING MATERIAL
Subj.758 Section 5 Page 5107 Issued:1972-02-03
  Revised:2014-05-20
Style 5107 Singke or Multiple conductor with other-than-extruded insulation

 
Rating 200 or 450 deg C, 600 Vac, Horizontal flame.
 
Conductor 26 AWG – 550 kcmil. Solid or stranded for sizes 26 – 8 AWG; Stranded only for larger sizes than 8 AWG.
 
Insulation Mica tape with braid, or Mica composite (see Facing Page) with braid.
  Conductor size Min average thickness of Mica tape Min average thickness of Glass Braid Treated with Silicone Varnish or TFE Finish
  26 – 12 AWG 25 mils 7 mils
  11 – 4 AWG 30 mils 15 mils
  3 – 4/0 AWG 35 mils 20 mils
  250 – 550 kcmil 40 mils 20 mils
 
Assembly Optional, two or more insulated conductors, may be cabled together with a max O.D. of 1.500 inches. A mica glass binder and/or fiberglass fillers may be employed.
 
Shield Optional, 36 – 30 AWG strands.
 
Covering Optional, over assembly, treated glass braid.
 
Standard Appliance Wiring Material UL 758.
 
Marking General.
 
Use Internal Wiring of high-temperature equipment where not subjected to repeated flexing and protected from mechanical abuse, and where the acceptability, including current-carrying capacity, has been determined by Underwriters Laboratories Inc.
 

UL and the UL Logo are trademarks of UL LLC © 2018 

 

Additional information

Weight 0.0048 lbs
Dimensions 1 × 0.125 × 0.125 in
Amp Rating
Number of Conductors
Manufacturer Part Number
Digi-Key Part Number
Manufacturer
Cord Length
Plug Type
spool-length
Stripe Color
Style/Rating

Gauge

Conductor

Color

, , , , , , , , , ,

Insulation

,

stranding

Temperature Rating

Voltage Rating